420Mdbs_Ir-F9 - Honeywell 301C Manuel De L'utilisateur

Masquer les pouces Voir aussi pour 301C:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

420MDBS_IR-F9

Group
Property
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
Notes
1 --
'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --
'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
1
Data Type
Required
R
enumerated
R
enumerated
R
character string
R
boolean
R
real
R
enumerated
O
boolean
R
boolean
R
boolean
R
R
enumerated
R
Storage
BACnet
2
Writeable?
Type
Modbus address * 256 + 1. For example an
C
N
420MDBS at Modbus address 002 will
appear as 513 or 0x0201.
C
N
analog_input (0)
if gas sensor fault Fault (1),
R
N
else normal (0)
"420MDBS GGGG AdXXX .GGGG " where
GGGG is the gas name and XXX is the
N
N
Modbus address. Values for gas name
include "NH3".
R
N
FALSE
R
N
Gas reading
As appropriate reports
R
N
no_fault_detected (0) or
unreliable other (7)
if alarm or fault "true" (1)
R
N
else "false" (0)
if faulty "true" (1)
R
N
else "false" (0)
R
N
"false" (0)
R
N
"false" (0)
Depends on configuration of 420MDBS
N
N
factory configuration or 301C configuration,
usually ppm (96)
93
Value
continued...

Publicité

Chapitres

Table des Matières
loading

Table des Matières