Objects for 301EM continued
Group
Property
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
active_text
status_flags
in_alarm
fault
overridden
out_of_service boolean
object_identifier
object_type
event_state
object_name
out_of_service
polarity
present_value
reliability
relinquish_default
status_flags
in_alarm
fault
overridden
out_of_service boolean
Notes
1 --
'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --
'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
Storage
Data Type
1
Required
Type
R
enumerated
R
enumerated
R
character string
R
boolean
R
enumerated
R
enumerated
0
character string
O
boolean
R
boolean
R
boolean
R
R
R
enumerated
R
enumerated
R
character string
R
boolean
R
enumerated
R
enumerated
R
enumerated
0
R
boolean
R
boolean
R
boolean
R
R
BACnet
2
Writeable?
For rel1, Modbus address * 256 + 8,
For rel2, Modbus address * 256 + 9,
For rel3, Modbus address * 256 + 10,
C
N
For rel4, Modbus address * 256 + 11
C
N
binary_values (5)
C
N
normal (0)
"VA301EM GGGG AdXXX .RelL " where
GGGG is the gas name, XXX is the Modbus
N
N
address and L is the relay number.
C
N
FALSE
R
N
current state of relay
C
N
not meaningful.
C
N
"ON"
C
N
not meaningful.
C
N
not meaningful.
R
N
always "false" (0)
always "false" (0)
R
N
For Buzzer, Modbus address * 256 + 24,
For Out1, Modbus address * 256 + 25,
For Out2, Modbus address * 256 + 26,
C
N
For Out3, Modbus address * 256 + 27
C
N
binary_value (5)
C
N
normal (0)
"VA301EM GGGG AdXXX.buzz"
"VA301EM GGGG AdXXX.out1"
"VA301EM GGGG AdXXX.out2"
"VA301EM GGGG AdXXX.out3"
where GGGG is the gas name, and XXX is
N
N
the Modbus address.
C
N
FALSE
C
N
always Normal (0)
R
N
state of buzzer and three 24VDC outputs.
C
N
not meaningful.
C
N
not meaningful.
C
N
not meaningful.
C
N
not meaningful.
C
N
always "false" (0)
always "false" (0)
C
N
89