Objects For 301Em - Honeywell 301C Manuel De L'utilisateur

Masquer les pouces Voir aussi pour 301C:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Objects for 301EM

Group
Property
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
Notes
1 --
'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --
'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
Storage
1
Data Type
Required
Type
R
enumerated
R
enumerated
R
character string
R
boolean
R
real
R
enumerated
O
boolean
R
boolean
R
boolean
R
R
enumerated
R
R
enumerated
R
enumerated
R
character string
R
boolean
R
real
R
enumerated
O
boolean
R
boolean
R
boolean
R
R
enumerated
R
BACnet
2
Writeable?
TxNumber * 256 + 1. The TxNumber is the
Modbus address plus the sensor number in
the 301EM. For example, sensor 2 on a
301EM at Modbus address 030 will appear
C
N
as 7937 or 0x1F01.
C
N
analog_input (0)
R
N
not meaningful
"VA301EM GGGG AdXXX .GGGG " where
GGGG is the gas name and XXX is the
Modbus address. Values for gas name
N
N
include "R11" and "NH3".
R
N
FALSE
R
N
Gas reading
As appropriate reports
no_fault_detected (0),
no_sensor (1), or
unreliable other (7)
R
N
Fault is detected within 60 seconds
R
N
not meaningful
if faulty "true" (1)
R
N
else "false" (0)
R
N
"false" (0)
R
N
"false" (0)
From 301EM, usually ppm (96)
N
N
For Amin, TxNumber * 256 + 2,
For Amax, TxNumber * 256 + 3,
For Bmin, TxNumber * 256 + 4,
For Bmax, TxNumber * 256 + 5,
For Cmin, TxNumber * 256 + 6,
For Cmax, TxNumber * 256 + 7
The TxNumber is the Modbus address plus
N
N
the sensor number in the 301EM.
C
N
analog_value (2)
C
N
not meaningful.
"VA301EM GGGG AdXXX.LLLL" where GGGG
is the gas name, XXX is the
Modbus address plus the sensor number in
the 301EM and LLLL is a member of the set
{Amin, Amax, Bmin, Bmax, Cmin and
N
N
Cmax}.
C
N
FALSE
Writing alarm thresholds over BACnet not
N
N
supported.
C
N
not meaningful.
C
N
not meaningful.
C
N
not meaningful.
C
N
always false (0)
C
N
always false (0)
ppm (96) or % (98)
C
N
88