Ec-Fx - Honeywell 301C Manuel De L'utilisateur

Masquer les pouces Voir aussi pour 301C:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EC-FX

Group
Property
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
Notes
1 --
'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --
'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
Storage
1
Data Type
Required
Type
R
C
enumerated
R
C
enumerated
R
R
character string
R
N
boolean
R
R
real
R
R
enumerated
O
R
boolean
R
R
boolean
R
R
boolean
R
R
R
R
enumerated
R
N
R
N
enumerated
R
C
enumerated
R
C
character string
R
N
boolean
R
C
real
R
N
enumerated
O
C
boolean
R
C
boolean
R
C
boolean
R
C
R
C
enumerated
R
C
R
N
enumerated
R
C
enumerated
R
C
character string
R
N
boolean
R
C
real
R
N
enumerated
O
C
boolean
R
C
boolean
R
C
boolean
R
C
R
C
enumerated
R
C
BACnet
2
Writeable?
Modbus address * 256 + 1. For example an
N
EC-F9 at Modbus address 003 will appear as
769 or 0x0301.
N
analog_input (0)
if gas sensor fault Fault (1),
N
else normal (0)
"EC-F9 GGGG AdXXX.GGGG" where GGGG
N
is the gas name and XXX is the Modbus
address. The gas name is often "NH3".
N
FALSE
N
Gas reading
As appropriate reports
no_fault_detected (0) or
N
unreliable other (7)
Fault is detected within 60 seconds
if faulty "true" (1)
N
else "false" (0)
if faulty "true" (1)
N
else "false" (0)
N
"false" (0)
N
"false" (0)
N
Usually ppm (96)
Modbus address * 256 + 2. For example an
N
EC-F9 at Modbus address 003 will appear as
770 or 0x0302.
N
analog_value (2)
N
normal (0)
"EC-F9 GGGG AdXXX.Amin" where GGGG is
N
the gas name and XXX is the Modbus
address. The gas name is often "NH3".
N
FALSE
Gas threshold. Synchronization is
maintained with the 301C and the EC-F9.
Y
Whichever value is written last is
distributed to the other two locations.
N
no_fault_detected (0)
N
always false (0)
N
always false (0)
N
always false (0)
N
always false (0)
N
Usually ppm (96)
Modbus address * 256 + 3. For example an
N
EC-F9 at Modbus address 009 will appear as
771 or 0x0303.
N
analog_value (2)
N
normal (0)
"EC-F9 GGGG AdXXX.Amax" where GGGG is
N
the gas name and XXX is the Modbus
address. The gas name is often "NH3".
N
FALSE
Gas threshold. Synchronization is
maintained with the 301C and the EC-F9.
Y
Whichever value is written last is
distributed to the other two locations.
N
no_fault_detected (0)
N
always false (0)
N
always false (0)
N
always false (0)
N
always false (0)
N
Usually ppm (96)
90
Value
continued...