Device Objects - Honeywell 301C Manuel De L'utilisateur

Masquer les pouces Voir aussi pour 301C:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

The tables on pages 75-97 are also available on the Honeywell
Analytics' Commercial Products CD that accompanied the 301C
Controller and from the Honeywell Analytics technical library
(www.honeywellanalytics.com > Products > Commercial Solutions >
301C > Technical Library).
Device Object
Group
Property
object_identifier
object_type
vendor_identifier
apdu_timeout
application_software_version
firmware_revision
max_apdu_length_accepted
model_name
number_of_apdu_retries
object_name
protocol_object_types_supported bit string
protocol_services_supported
protocol_version
segmentation_supported
system_status
vendor_name
protocol_revision
database_revision
Notes
1 --
'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --
'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
Storage
1
Data Type
Required
unsigned
R
enumerated
R
enumerated
R
unsigned
R
character string
R
character string
R
unsigned
R
character string
R
unsigned
R
character string
R
R
bit string
R
unsigned
R
enumerated
R
enumerated
R
character string
R
unsigned
R
unsigned
R
75
BACnet
2
Type
Writeable?
N
N
Set from LUI
C
N
device (8)
C
N
Honeywell Inc. (17)
C
N
0
C
N
"1.1"
C
N
"1.3.18"
C
N
1476
C
N
"301C-BIP"
C
N
0
N
N
default "VA301C:1", settable from LUI.
analog_input,
analog_output,
analog_value,
C
N
binary_input,
binary_value,
device
readProperty,
readPropertyMultiple,
writeProperty,
deviceCommunicationControl,
reinitializeDevice,
C
N
i_Am,
i_Have,
timeSynchronization,
who_Has,
who_Is,
C
N
1
C
N
no_segmentation (3)
C
N
operational (0)
C
N
Honeywell
C
N
2
C
N
not meaningful
Value

Publicité

Chapitres

Table des Matières
loading

Table des Matières