Do not open and wire the transmitter with the power supply connected.
-
It is obligatory to put security devices close to the transmitter, on:
-
Power supply : 18-32VDC - 250mA fuse and interrupter
Relay :
Do not apply both a dangerous voltage and a very low safety voltage to
-
the relays.

3.4.1 8175 Compact version with an EN 175301-803 connector

2
3
1
5
Fig. 3.3 Plug assembly
Wiring
Orange
To position SW2,
see 3.4.2, compact
version with cable
gland
Green/Yellow
To the earth lug of the housing
INSTALLATION
115/230VAC - 5A fuse and a bipolar interrupter
3A fuse max. and a bipolar interrupter
(depending on the application).
1.
To open the connector remove screw 1 (Fig. 3.3).
2.
Remove the internal part 3 from the external casing 2.
4
3.
Connect the transmitter according to the pin
assignment in Fig. 3.3
4.
When re-assembling, the internal part 3 can be rotated
in 90° steps to a desired position before inserting back
into the casing 2.
5.
Tighten the cable gland 5. Then place gasket 4
between the EN 175301-803 connector and the fixed
connector of the transmitter and plug the
EN 175301-803 connector onto the transmitter.
6.
Tighten screw 1.
Red
Black
Brown
1
2
3
4
+
-
+ (L+; 18-
32 VDC)
14
EN 175301-803
1
I (4-20 mA output)
3
2
- (L-)
(*)
(*) If direct earthing is
impossible, connect a
+ -
100 nF/50 V-condensa-
tor between the negative
terminal of the power
Power supply
supply and the earth.
8175