7.4 Reducing Wall and Ceiling Clearances Safely

It is often desirable to reduce the
minimum installation clearances by
placing the stove closer to walls so
the installation takes up less floor
space. You can safely reduce the
minimum
permanently installing a shield
between
the
combustible material. The rules for
safe shields can be complicated,
so read them carefully and follow
them exactly. Note that there may
be minor regional differences in
clearance reduction rules so be
sure to check with your building or
fire inspector before proceeding.
Solution 3.5 Installation and Operation Manual
Stove Builder International Inc. | 44826 | Rev: May 31 2019 2:49PM | Uncontrolled Copy
clearances
by
stove
and
Important Note: Addition required to
the floor protection when the stove is
installed in a mobile home and
assembled on legs version only:
In addition to meeting the minimum size
of the floor protection, the stove must be
placed on a podium having a maximum
dimension of 30" (762 mm) x 24" (610
mm) and a minimum height of 2" (51
mm). This podium can be constructed of
combustible materials as long as it is
covered of non-combustible materials.
See figure beside.