Hitachi RAF-25NH4 Données Techniques page 241

Masquer les pouces Voir aussi pour RAF-25NH4:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

NSPECT NG EXTERNAL ELECTR CAL PARTS
¥ Check to see that the LED is either on or blinking.
¥ LEDs are divided between those for A cycle and those for B cycle. This is determined by either an A or a B appearing in the
circuit code, for example LD301A or LD301B.
¥ Carry out inspections by examining the on/ blinking status of LEDs 301-304.
LED number
LD301
Name
Diagnosis
lamp 1
Case 1
Off
Case 2
Blinks once
Case 3
Blinks
Case 4
On
Case 5
Off
(blinks once)
Case 6
Off
Case 7
On
Case 8
Off
Case 9
On
LD302
LD303
Diagnosis
Communications
lamp 2
lamp
Off
Off
Off
Off
Off
Off
Blinks
Off
Off
Blinks
Off
Off
Off
Off
On
Off
On
Off
COMPRESSOR
SIDE  A.
L
L
L
L
D
D
D
D
3
3
3
3
0
0
0
0
1
2
3
4
A
A
A
A
SERVICE  SWITCH
LD304
Status
Operation
lamp
Normal off status or
Off
unconnected
microcomputer power
source
Microcomputer reset
Off
status (immediately
after inserting power
source or immediately
after power source
abnormally)
Off
Abnormally stop
Thermistor abnormally
Off
Off (blinks)
Communications error
On
Normal operation
On
OVL1 operation
On
OVL2 operation
On
OVL3 operation
COMPRESSOR
SIDE  B.
L
L
L
L
D
D
D
D
3
3
3
3
0
0
0
0
1
2
3
4
B
B
B
B
C1D1
C2D2
C3D3
C4D4
INDOOR  1
INDOOR  2
INDOOR  3
INDOOR  4
260
Checkpoints
If the LED is not on even when the
power source is connected, the
microcomputer power source is
unconnected.
Inspection method 1
It is normal for LD301 to blink once
after the power source has been
inserted. If the unit stops when it is in
operation and LD301 blinks once, it is
possible that the power source has
been temporarily interrupted by
lightening or for some other reason.
Replace the control PCB if this occurs
frequently.
Abnormally stop is shown by the
number of times the LED blinks.
Inspection method 2
Thermistor abnormally is shown by
the number of times the LED blinks.
Inspection method 3
Communications error is shown
by the number of times the LED
blinks.
Inspection method 4
*In the case that an internal unit is
not connected, the number of
connected internal units is
shown by the number of times
the LED blinks. This is not a
abnormally. The internal unit
has no communications error
and is able to operate normally.
Normal operation
Normal operation
Normal operation
Normal operation
L
N