Room temperature
Temperature set for cooling and
dehumidifying (value set by remote
control: (+) SHIFTC)
Fan speed set to ÒautoÒ
Start
Start/stop switch
Thermo judgment
Ultra-Hi
Hi
Indoor fan
Med
Lo
Ultra-Lo
Operation lamp
1min.
Max.
Rating
3000
Min.
0
Lo
Outdoor fan
Reversing valve(cooling ÒonÒ mode)
Notes:
(1) The comprassor minimum ON time and minimum OFF time is 3minutes.
(2) See ÒDamper control theoryÒ for dampar control and upper / lower fan operations.
asic Cooling Operation
Stop
Start
15sec.
Lo
CLMXTP
Stop
Thermo OFF
(Engaged in the set fan speed in cases other than ÒautoÒ fan speed)
1min.
15sec.
15sec.
Lo
Table 1 Æ TCMAX
Room
Maximum speed
temperature-set
-minimum speed
temperture
(including shift)
1400min -
1
2.00ûC
1800min -
1
2.33ûC
2200min -
1
2.66ûC
2600min -
1
3.00ûC
3000min -
1
3.33ûC
3400min -
1
3.66ûC
3800min -
1
4.00ûC
4200min -
1
4.33ûC
4600min -
1
4.66ûC
5000min -
1
5.00ûC
5400min -
1
5.33ûC
5800min -
1
5.66ûC
6200min -
1
6.00ûC
6600min -
1
6.33ûC
7000min -
1
6.66ûC
Note:
1. See the data on page 118, 120, 123 for each constant
in capital letters in the diagrams.
127