Maintenance And Repair Of Equipment; Introduction; Equipment Maintenance; Equipment Repair - ENAG CDS Série Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ENAG
Maintenance and repair of the equipment

4.1 Introduction

This section deals with arrangements for maintenance and repair of the equipment.
Correct operation and the life of the product are conditional on strictly complying
with the recommendations below.

4.2 Equipment maintenance

Disconnect the battery charger from the alternating mains supply for all
maintenance operations.
If the charger is placed in a dusty environment, vacuum it periodically to clean it
since layers of dust might affect heat dissipation.
Check the state of charge of the batteries every three months.
An annual check that nuts and bolts are tight is necessary in order to guarantee
correct functioning of the charger (especially in an environment subject to
vibration, shock, large changes in temperature, etc.).
A complete technical examination by a ENAG recommended serviceman is
advisable every 5 years. This general technical examination can also be carried
out in our factories.

4.3 Equipment repair

Disconnect the battery charger from the ac mains supply and from the batteries
before carrying out any repairs.
If a fuse has blown, make sure the replacement complies with the rating and type
of fuse recommended in section 2.1.
For any other repair action, contact a reseller or ENAG.
CDSDEB
Page 56

Publicité

Chapitres

Table des Matières
loading

Table des Matières