3.3 Additional supplies necessary for electrical installation

These items do not form part of ENAG's supply.
References to additional supply items which are necessary for correct operation of
the charger are defined in the following sections:
Any failure to comply with these provisions will result in cancellation of the
manufacturer's guarantee.

3.3.1. Cable connecting to the public mains supply or to an electricity generating set

Depending on line lengths, cables connecting to the ac mains supply MUST have a
cross-section equal to, or greater than, the values shown in the table below:
Model
SEEL005322
SEEL005324
SEEL005326
SEEL005328
SEEL005330
SEEL005332
SEEL005336
SEEL005338
SEEL005342
SEEL005344
SEEL005348
SEEL005350
SEEL005354
SEEL005356
SEEL005358
It is ESSENTIAL to use endfittings with insulated sleeves (in accordance with standard
NF G 63-023) for connecting the mains input.
The PE conductor (commonly called "earth" green/yellow wire) of the ac source MUST
be connected to the charger on the terminal provided for this purpose.
CDSDEB
Minimum cross-section
and types of cable for
115 Vac
Supplied
3 x 1.5 mm²
HO7-VK
3 x 2.5 mm²
HO7-VK
3 x 2,5 mm² HO7-VK
3 x 4 mm² HO7-VK
3 x 4 mm² HO7-VK
3 x 4 mm² HO7-VK
Minimum cross-section
and types of cable for
230 Vac
Supplied
3 x 1.5 mm²
HO7-VK
3 x 1.5 mm²
HO7-VK
3 x 1,5 mm² HO7-VK
3 x 2,5 mm² HO7-VK
3 x 2,5 mm² HO7-VK
3 x 2,5 mm² HO7-VK