3.3.2. Battery connection cable

Depending on line lengths, cables connecting to the batteries MUST have a cross-
section equal to, or greater than, the values shown in the table below:
Model
SEEL005322
SEEL005324
SEEL005326
SEEL005328
SEEL005330
SEEL005332
SEEL005336
SEEL005338
SEEL005342
SEEL005344
SEEL005348
SEEL005350
SEEL005354
SEEL005356
SEEL005358
It is ESSENTIAL to use the cable glands on the underside of the case in order to
prevent any damage to the cables on the metal edges of the case and to guarantee
double insulation between the live conductors and electrical earth.

3.3.3. Voltmeter and Ammeter link cable (only on certain models)

These cables must have a cross-section equal to, or greater than, 0.34 mm² and be of
type: KZ0506 - 600 V.
They must have endfittings with insulating sleeves in accordance with NF G 63-023.
It is ESSENTIAL to use the cable glands on the underside of the case in order to
prevent any damage to the cables on the metal edges of the case and to guarantee
double insulation between the charging circuit and electrical earth.
CDSDEB
Cross-section and type
of battery connection
cables
2.5 mm² HO7-VK
1.5 mm² HO7-VK
4 mm² HO7-VK
2.5 mm² HO7-VK
6 mm² HO7-VK
4 mm² HO7-VK
10 mm² HO7-VK
6 mm² HO7-VK
16 mm² HO7-VK
10 mm² HO7-VK
16 mm² HO7-VK
10 mm² HO7-VK
25 mm² HO7-VK
16 mm² HO7-VK
16 mm² HO7-VK
Type of terminal
Cross-section of cable and
diameter of the terminal hole
Endfittings with insulated sleeves
MUST be fitted (in accordance
with standard NF G63-023)
6 mm² - 4 mm
4 mm² - 4 mm
10 mm² - 4 mm
4 mm² - 4 mm
16 mm² - 5 mm
10 mm² - 5 mm
16 mm² - 6 mm
10 mm² - 6 mm
25 mm² - 6 mm
16 mm² - 6 mm
16 mm² - 6 mm
Page 51