The cable linking the installation to earth MUST be connected to the earth screw
situated inside the charger.
The cable used must have a minimum cross-section of 2.5 mm², be of the type HO7-
VK and be fitted with a suitable terminal.

3.4 Special recommendations for installation

3.4.1. Case position

3.4.1.1. Preventing the charger overheating
The charger is designed to be mounted on a vertical wall as shown on page 36,
37 and 39.
An area of 150 mm from the sides, top and bottom of the case should be kept
clear.
Cooling is provided by forced ventilation on certain models. The installer must
make the necessary arrangements to ensure that the temperature of the air at
entry (see drawing on pages 36 and 37) is less than 40°C in extreme operating
conditions.
Arrangements must also be made to ensure hot air can get away either side of
the charger.
3.4.1.2 Preventing running water or spray falling on the charger
The protection factor is IP22 and the charger position must be chosen so as to
prevent any moisture or salt entering the charger.
If this were to occur, the equipment would be irreversibly damaged and there
would be a potential risk to the user.
You are recommended to position the charger in a dry, well-ventilated location,
away from any source of heat.
3.4.1.3 Arrangements for the batteries
Batteries connected to the charger are likely to give off explosive gases during
the charging phase.
You are therefore recommended:
to ban the use of any equipment generating sparks and flames near to the
batteries.
to position the batteries in a well-aired and ventilated location.
to take note of the battery manufacturer's instructions when installing the
batteries.
CDSDEB
Page 52