2.1.3.2 Current
The table below defines the maximum output current at rated output power as well
as the type and rating of the fuses placed in series with the charger outputs.
Model
SEEL005322
SEEL005324
SEEL005326
SEEL005328
SEEL005330
SEEL005332
SEEL005336
SEEL005338
SEEL005342
SEEL005344
SEEL005348
SEEL005350
SEEL005354
SEEL005356
SEEL005358

2.1.4 Environmental specification

All chargers in the range meet the following characteristics:
Storage temperature: - 20°C to + 70°C.
Operating temperature: 0°C to + 40°C.
Humidity: < 90% non-condensing

2.1.5 Protection and operating safety

2.1.5.1 Input protection

Models CDS 70, CDS 120, CDS 190 and CDS 300 are fitted with two pole
protection by 2 fuses F1 and F2 whose ratings are given in section 2.1.2.
All other models are fitted with single pole protection by a fuse F1 whose rating is
given in section 2.1.2.
Maximum output
current
6 A
3 A
10 A
5 A
16 A
8 A
25 A
12 A
40 A
20 A
60 A
30 A
80 A
50 A
60 A
CDSDEB
Fuse rating
7,5 A
5 A
15 A
7,5 A
20 A
10 A
25 A
15 A
2 x 20 A
20 A
3 x 20 A
2 x 15 A
4 x 20 A
2 x 25 A
3 x 20 A
Page 43
Type of fuse
25707.5 LITTLEFUSE
257005 LITTLEFUSE
257015 LITTLEFUSE
25707.5 LITTLEFUSE
257020 LITTLEFUSE
257010 LITTLEFUSE
257025 LITTLEFUSE
257015 LITTLEFUSE
257020 LITTLEFUSE
257020 LITTLEFUSE
257020 LITTLEFUSE
257015 LITTLEFUSE
257020 LITTLEFUSE
257025 LITTLEFUSE
257020 LITTLEFUSE