** The charge stops if this alarm occurs.

6.3.2 Battery charger alarms

The remote display reports the following alarms:
- Fan failure
- Parallel fault (if enabled)
- Output fuse break-down
- Battery temperature out of range (if temperature probe <10°C or >50°C)
- Output short-circuit or overload
- The charger voltage (before distribution) is below 11V ± 5% (for 12V
models) or 22V ± 5% (for 24V models) for more than 10 seconds. Hysteresis
is approximately 0.5V.
2
1 : Auto Start : if AC is available and charge is
OFF, this function automatically starts the
charge if a battery low alarm occurs
2 : Home (return to main page)
3 : AC High : overvoltage alarm can be set
1
down to 265V.
4 : AC Low : overvoltage alarm can be set up
to 85V.