Installation; Charger Overall Dimensions; Wiring; Cable From The Public Ac Power Supply Network Or Generator - ENAG CDS4 12V/25A Manuel Utilisateur

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
3

INSTALLATION

This paragraph deals with installation of the equipment.
Installation and initial commissioning should be carried out by an electrician or professional installer in accordance
with the standards currently in force (for small craft the applicable international standard is ISO13297).
The installer should familiarize himself with this operating manual and inform users of the instructions for use and the
safety warnings set out in the manual.
3.1
C
HARGER OVERALL DIMENSIONS
Chargers CDS4 12-25 and 24-12 - See appendix 3
Chargers CDS4 12-40 and 24-20 - See appendix 4
Chargers CDS4 12-60 and 24-30 - See appendix 5
3.2
W
IRING
When connecting or disconnecting a cable, the charger's power supply must be turned off and the batteries
electrically insulated from the charger.
The references for additional cables and connectors required for the appliance to operate efficiently are provided in
the following paragraphs : failure to comply with these provisions renders the warranty null and void.

3.2.1 Cable from the public AC power supply network or generator

Disconnect AC network before any wiring and connecting of the connector.
All CDS4 battery chargers can operate automatically on single phase networks from 90 to 265VAC and from 47 to
65Hz.
Generators
The ENAG battery chargers are designed to operate from a generator.
Be careful : In some cases, the generators can produce high over voltages, in particular during start up
phase. Before connecting the charger, please check its compatibility with the characteristics of the
generator : power, voltage, overvoltage, frequency, current, etc.
It is highly advised to disconnect the charger from the AC network during the generator starting phase.
Any damage to the charger due to a voltage surge will be excluded from warranty.
Depending on cable lengths, the cross-section of AC power cables must be at least equal to or greater than the values
provided in the table below :
Model
CDS4 12-25 and 24-12
CDS4 12-40 and 24-20
CDS4 12-60 and 24-30
CDS4-1M-2M-G - 03 EN.docx
Minimum cross-section for
115VAC
3 x 2.5 mm²
Minimum cross-section
for 230VAC
3 x 1.5 mm²
3 x 1.5 mm²
3 x 1.5 mm²
24

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Cds4 12v/40aCds4 12v/60aCds4 24v/12aCds4 24v/20aCds4 24v/30a

Table des Matières