3.3.4 Factory setting

The charger's factory settings are:
Sealed type battery (lead sealed)
BOOST in ON position
REFRESH in OFF position
This setting is a compromise for satisfactory recharging of different technologies of batteries :
-
Opened classic lead
-
Sealed, Gel or AGM
-
Spiral sealed
-
Lithium Iron Phosphate ( LiFePO4 ) with BMS
To define the charge in function of your battery, please refer to the chart, paragraph : 3.3.2.
The installer should set the switches (excluding input and output voltage) and possibly adjust the output voltage with
no load using potentiometer R432 (use the appropriate tool to turn the screw of the potentiometer), depending on :
-
the type of battery (contact the battery manufacturer if necessary)
-
the intended usage
-
the cross-section and length of the output cables
-
whether or not the boost function is required
For special batteries, call in a professional installer, who will make the specific settings in accordance with the battery
manufacturer's specifications and according to the specifics of the installation.
ENAG in not liable for any damage caused to the batteries or for inefficient recharging.