ADDITIONAL INFORMATION

7.1
E
XTERNAL POWER SUPPLY
It is possible to use an external power supply in
order to supervise batteries when AC network is off.
7.2
M
ONITOR AND
7.3

UPDATING THE SOFTWARE

In case a newer firmware is available for the display monitor, it can be easily updated. Therefore, the new firmware
file has to be put on a Micro SD-card (Please use a micro SD-card with max. 4 GB). Then, the SD-card shall be inserted
into the holder on the top side of the display monitor and the unit has to be restarted from DC power. The updating
process will start automatically. After that, the SD-card shall be removed again.
7.4

LIMITED FUNCTIONS AVAILABLE

Depending on the model of charger and revision number, some functions like individual battery setting via the display
may not be available.
7.5
E
QUIPMENT REPAIRS
Disconnect the battery charger from the AC power network and disconnect the batteries before undertaking any
repairs.
In case of fuses blowing, respect the calibre and type of fuse recommended in this manual.
Please contact ENAG or their distributor for any other repairs.
Any repair without ENAG prior agreement entails an exclusion of warranty.
R
EAD ONLY MODE
1
When chargers are used in parallel, only a single
display can operate into Monitor mode. All other
displays shall be configured into Read only mode ; In
this mode, the display cannot control the battery
charger anymore. This mode is symbolized with a
lock onto the main page [1].
When the monitor enters
into stand-by, the
Read-only displays will
stop to emit information.