left side of the fi replace. Be sure to place the Tali on a solid fl oor plumb under the fl ue pipe.

Insulation

Due to the high temperatures of the exterior walls (up to approximately 150 °C or 300 °F) it is prohibited to have or to place any
combustible materials close to the fl ue system. The entire concentric pipe system should be encased with fi reproof material
from the place where it is out of sight up to the outlet in the exterior wall. Ventilate the encased concentric pipe system by
placing a grate near the fl oor and the ceiling on every fl oor. Use universal wall clips with a diameter of 150 mm for anchoring
the concentric pipe system.
If an existing chimney is used, fi rst make sure whether the chimney is suffi ciently insulated and is wide enough
to accommodate the concentric pipe system. If the chimney was previously used as a wood-burning or coal-fi red
stove, it must fi rst be professionally cleaned. You must use special WANDERS connecting sets for connecting a
gas hearth to an existing chimney.

Gas connection

Use a feed pipe with an approved G3/8" stop cock with coupling.
De-aerate the supply pipe before fi tting and fastening the appliance.
Avoid tension on the operating valve and pipes to avoid gas leakage.
Check if the connection is gastight.

Placing the concentric channel system

The combination of the device and the Wanders (M&G or Schiedel Metaloterm) concentric fl ue system (Ø 100 mm - Ø 150
mm) is approved in accordance with the European CE directive for appliances burning gaseous fuels. Therefore, only this
system may be used in combination with the device. The warranty on the device expires if it is (partly or completely) installed
in combination with a diff erent channel system. The Wanders (M&G or Schiedel Metaloterm) concentric channel system (Ø 100
mm - Ø 150 mm) can be used in new construction as well as existing chimneys.

Bracketing the channel

Secure the concentric system with several approved mounting brackets, so that the device does not bear the weight of the
channel system. Keep the following in mind;
Place the fi rst mounting bracket no more than 0.5 metres from the device.
Place a mounting bracket no more than 0.1 metres away from every bend, in the event that there is more than 0.25 metres
between two bends. If two bends are less than 0.25 metres apart, only 1 mounting bracket will have to be placed between
the bends.
Place a mounting bracket on horizontal and diagonal parts at at least 1-metre intervals.
Place a mounting bracket on vertical parts at at least 2-metre intervals. Make sure to secure a roof duct with guy wires if it
protrudes from the duct by more than 1.5 metres. Use four screws to secure the façade duct on the outside.
Instructions for placing the outfl ow
The outfl ow of the pipe system can be placed on top of the roof or against the side wall of the house.
Outfl ow on top of the roof
When placing the outfl ow on top of the roof, make sure
that there is a distance of at least 50 cm between the
outfl ow and the edges of the roof, with the exception
of a possible existing ridge. You must also take the place
of the outfl ow into account in relation to the existing
ventilation openings, movable windows and combustion
air supply provisions. Please consult the national and local
requirements.
20
Min.
50 cm