7.4 Auxiliary output undelayed flashing (RLU)

(S3 = «OFF» or S4 = «OFF»; S5 = «ON»)
With this DIP switch, flashing of the auxiliary output AUX1 and AUX2 can be activated on mode RLU.
Output
Aux. Relay
1,5 s 1,5 s

7.5 Auxiliary output delayed (RL)

(S3 = «ON» or S4 = «ON»)
In this operating mode, the respective auxiliary output is activated with a delay of approx. 0.5 second and
then remains active for max. 3 seconds if an error is signalled.
Output
Aux. Relay
0,5 s

8. Mechanical mounting

The switching unit must be professionally mounted:
- In a dust- and moisture-protected switching cabinet or housing.
- Installation in a Pollution Degree 2 environment.
- With a protection class of at least IP54.
- On a 35 mm DIN mounting rail acc. to EN 50 022.
The switching unit must not be mounted in the immediate vicinity of strong sources of heat.
The switching unit may be mounted in any orientation.
Safety output (symbolic)
Auxiliary output (symbolic)
Safety output (symbolic)
Auxiliary output (symbolic)
3 s