Wiring Diagram For Modbus - Maico WS 320 Série Notice D'installation

Masquer les pouces Voir aussi pour WS 320 Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

18 Wiring diagram for ModBus

– circuit board A2 –
A
Ventilation unit
A1
Electronic slide-in module
A2
CDV unit control
W11 Connecting cable for ModBus
(provided by customer), e.g.
LIYY 3 x 0.25 mm²
ModBus mode RTU
Baud rate
9600/19200
Data bits
8
Parity
Even
Stop bits
1
Address
10 (basic setting)
18 Wiring diagram for ModBus – circuit board A2 – | UK
A
A1
A2
GND
W11
B
A
If the comfort control unit is deactivated in the
parameter menu (touchscreen control unit
RLS T1 WS), the connection terminals on the
RS 485 terminal block can be used as the
ModBus interface. The controlled domestic
ventilation unit can thereby be incorporated
into a building control technology.
63

Publicité

Table des Matières
loading

Table des Matières