4. Modify decentralised units
AR or QD AL, depending on installation
situation.
Pos. I: Condition upon delivery
Pos. III: Modification as follows
Possible installation positions: lengthwise
[I] or through the unit base [III].
Modification to Pos. III: Remove cover
[A], take out plate [B] and insulation [C] (if
necessary, use knife to cut out insulation
around the knockout point). Remove so-
cket [S] and fit in new position. Fit parts [C]
and [A] at previous socket position.
5. Connect air channels  note chapter 10.7.
6. Fit front cover  chapter 10.2.
7. For QD AR and QD AL units, screw down
the hood with all 4 screws.
10.6 Installing condensate drain
310/410
320/470
NOTICE
Without a siphon, the ventilation unit will draw
in air through the drain pipe. Always install a
siphon (1½" external thread). Never fit several
siphons one after another without a pipe
divider.
NOTICE
Bacterial attacks are possible if a siphon is
fitted without a drip funnel as the siphon is
not then disconnected from the wastewater
system. Siphon needs seal water drop of at
least 50 mm. Install an open drip funnel with
another siphon at the drain end.
Trio
QD
1. Remove front plate and front cover
2. Fit a siphon and open drip funnel on the
3. If the humidity level in the installation room
4. Fill drain with water, check seal integrity
5. Fit siphon with drip funnel and seal water
6. Fit front cover and front plate  chap. 10.2.
NOTICE
Without a siphon, the ventilation unit will draw
in air through the drain pipe. Be sure to install
a siphon. Never fit several siphons one after
another without a pipe divider.
Condensation is produced during heat reco-
very and has to be removed correctly via the
condensation drain.
1. Release the two quick-release clips and
Figure: Right-hand version of ventilation unit,
left-hand version is mirror image
 chapter 10.2.
condensate drain.
is disproportionately high, insulate the
drain and condensate drain connector to
avoid condensate.
and drainage. Fill the siphon up with water
after long dry periods too.
drop of at least 50 mm.
170
remove the front cover.
10 Installation | UK