Alarm
A59
Description
The backfeed protection has been activated. Alarms present only in the
history log.
➢ Problems on the bypass static switch
Possible
causes
Solutions
1. Check the static switch thyristors
2. Contact our Technical Support Service.
Alarm
A61
Description
Failure of the redundant auxiliary power supply .
➢ Internal fault.
Possible
causes
Solutions
1. Contact our Technical Support Service.
Alarm
A62
Description
Sudden increase of the AC input voltage (fast sensor)
➢ Voltage spike on the AC mains.
Possible
causes
➢ Possible internal fault.
Solutions
1. Check the mains voltage.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A63
Description
During the UPS start-up a failure prevented the proper execution of the
sequence.
➢ Control devices in wrong position or operated improperly.
Possible
causes
➢ Possible internal fault.
Solutions
1. Make sure the position of the control devices (isolators, selectors)
2. If the alarm persists, contact our Technical Support Service.
Alarm
A64
Description
Sudden drop of the AC input voltage (fast sensor)
➢ Voltage drop on the AC mains (brown-out).
Possible
causes
➢ Possible internal fault.
Solutions
1. Check the mains voltage.
2. If the alarm persists, contact our Technical Support Service.
Manuel de l'utilisateur de l'ASI
BACKFEED RELAY ON
LOSS OF REDUNDANT POWER SUPPLY
MAINS OVERVOLTAGE
START SEQ BLOCK
is as specified in the procedures (see "Installation and start-up"
section).
MAINS UNDERVOLTAGE
UPS user manual
Utilizzo dell'UPS
OMP06145 REV. D
59