COMMON ALARM
Common alarm.
➢ At least one alarm is present.
1. Check which alarms are present and carry out the indicated
procedures.
A31
MBCB BUS CLOSED
The manual bypass isolator is closed.
➢ Manual bypass isolator closed.
1. Check the status of the manual bypass isolator.
2. Check the functionality of the auxiliary contact of the isolator.
3. If the alarm persists, contact our Technical Support Service.
A32
EPO BUS CLOSED
The system is blocked due to the activation of the emergency power off
button.
➢ Activation of the (local or remote) emergency power off button.
1. Release the emergency power off button and reset the alarm.
2. If the alarm persists, contact our Technical Support Service.
A33
ASYMMETRIC LOAD
The positive and negative voltages measured on the DC capacitors
towards the middle point are different.
➢ Possible failure on the measuring circuit.
➢ Possible fault of DC capacitors.
1. Reset the system.
2. If the alarm persists, contact our Technical Support Service.
A34
SERVICE REQUIRED
A UPS check is necessary.
➢ Possible UPS fault.
1. If the alarm persists, contact our Technical Support Service.