Status
Description
Operating
condition
Status
Description
Operating
condition
Status
Description
Operating
condition
Status
Description
Operating
condition
Status
Description
Operating
condition
Status
Description
Operating
condition
46
OMP06145 REV. D
UPS user manual
Manuel de l'utilisateur de l'ASI
Utilizzo dell'UPS
S8
INV MASTER SYNC
The inverter is synchronized with the MASTER UPS.
This status is only present on the SLAVE UPS units, and shows that the
inverter is synchronized with the signal sent by the MASTER UPS.
S10
RECT STANDBY (NOT AVAILABLE)
The rectifier is in standby mode.
The rectifier is off and ready to be started to charge the battery (Green
Conversion algorithm).
S11
INV STANDBY (NOT AVAILABLE)
The inverter is in standby mode.
The inverter is off and ready to be started in case of anomaly of the
bypass mains.
S12
BATT STANDBY (NOT AVAILABLE)
The battery is in standby mode.
The battery static switch is open and the battery is disconnected from
the DC bus.
S14
BATT CHARGE I
The battery is charging.
The battery static switch is closed and the battery is in the first phase of
the I/U charging mode (DIN 41773), with constant current and
increasing voltage.
S15
BATT CHARGE U
The battery is charging.
The battery static switch is closed and the battery is in the second and
final phase of the I/U charging mode (DIN 41773), with constant voltage
and decreasing current.