SSI FAULT
The system has detected a failure in the static inverter switch.
➢ Possible problems on the loads.
➢ Static switch fault.
1. Check the absorption of the loads and the presence of DC
components, if any, on AC current.
2. If the alarm persists, contact our Technical Support Service.
A41
RECT ERROR LOOP
The control is not able to regulate the rectifier output voltage precisely.
➢ Regulation system failure.
1. Reset the system.
2. If the alarm persists, contact our Technical Support Service.
A44
DESATURATION (NOT AVAILABLE)
The inverter is blocked due to the operation of the desaturation sensor
of the IGBT drivers.
➢ Inverter bridge fault.
1. Reset the system.
2. If the alarm persists, contact our Technical Support Service.
A45
HIGH TEMPERATURE SSW
High temperature of the heat sink on the static switch.
➢ Fault of the heat sink cooling fans.
➢ The room temperature or cooling air temperature is too high.
1. Check the fans operation.
2. Clean the ventilation grids and the air filters, if any.
3. Check the air conditioning system (if present).
4. If the alarm persists, contact our Technical Support Service.