Setting of all important parameters

Before commissioning, set important operating parameters with the potentiometers and the stepping
switch:−25−
l
the rated motor current with the stepping switch
l
the acceleration time with potentiometer "T"
l
the starting voltage with potentiometer "U
Stepping switch [S]
Position
Rated current
0
1
1.0 A
2
1.4 A
3
1.8 A
4
2.4 A
5
3.0 A
6
4.0 A
7
5.5 A
8
7.0 A
9
9.5 A
Setting
1.
Set the rated motor current with the
stepping switch
Lenze setting: 1 = 1.0 A
2.
Set the acceleration time t
potentiometer T"
Lenze setting: approx. 1.5 s
3.
Set the starting voltage U
potentiometer U
0"
Lenze setting: approx. 50 %
)
Note!
In multi−motor operation, the settings apply to both motors.
You can use the hand terminal to individually adjust the parameters to each
motor.
100
"
0
Lenze motor power with mains voltage
3/PE 230 VA
3(/N)/PE 400
C
VAC
0.25 kW
0.37 kW
0.25 kW
0.55 kW
0.37 kW
0.75 kW
0.55 kW
1.1 kW
0.75 kW
1.5 kW
1.1 kW
2.2 kW
1.5 kW
3.0 kW
2.2 kW
4.0 kW
with
ir
0
with
0
0
U
out
100%
U
start
0
0
EDK71MMXXX−020 DE/EN/FR 5.0
Comment
3(/N)/PE 500
VAC
2
No I
0.37 kW
0.55 kW
0.75 kW
1.1 kW
1.5 kW
2.2 kW
3.0 kW
4.0 kW
5.5 kW
Comment
l
OFF
l
0
3.0 A
start032
Use the hand terminal to
check or change the setting
3.00 s
start012
in C0012
l
100.0 %
start008
l
t
start028
t monitoring
See also ^ 81
Use the hand terminal to
check or change the
setting in C0120
With U
= 100 %, the
0
acceleration time t
is
ir
deactivated
Use the hand terminal to
check or change the
setting in C0016
L

Publicité

Table des Matières
loading

Table des Matières