6
Setting of all important parameters
Before commissioning, set important operating parameters with the potentiometers and the stepping
switch:−25−
l
the rated motor current with the stepping switch
l
the acceleration time with potentiometer "T"
l
the starting voltage with potentiometer "U
Stepping switch [S]
Position
Rated current
0
–
1
1.0 A
2
1.4 A
3
1.8 A
4
2.4 A
5
3.0 A
6
4.0 A
7
5.5 A
8
7.0 A
9
9.5 A
Setting
1.
Set the rated motor current with the
stepping switch
Lenze setting: 1 = 1.0 A
2.
Set the acceleration time t
potentiometer T"
Lenze setting: approx. 1.5 s
3.
Set the starting voltage U
potentiometer U
0"
Lenze setting: approx. 50 %
)
Note!
In multi−motor operation, the settings apply to both motors.
You can use the hand terminal to individually adjust the parameters to each
motor.
100
"
0
Lenze motor power with mains voltage
3/PE 230 VA
3(/N)/PE 400
C
VAC
–
–
–
0.25 kW
–
0.37 kW
0.25 kW
0.55 kW
0.37 kW
0.75 kW
0.55 kW
1.1 kW
0.75 kW
1.5 kW
1.1 kW
2.2 kW
1.5 kW
3.0 kW
2.2 kW
4.0 kW
with
ir
0
with
0
0
U
out
100%
U
start
0
0
EDK71MMXXX−020 DE/EN/FR 5.0
Comment
3(/N)/PE 500
VAC
2
–
No I
0.37 kW
0.55 kW
0.75 kW
1.1 kW
1.5 kW
2.2 kW
3.0 kW
4.0 kW
5.5 kW
Comment
l
OFF
l
0
3.0 A
start032
Use the hand terminal to
check or change the setting
3.00 s
start012
in C0012
l
100.0 %
start008
l
t
start028
t monitoring
See also ^ 81
Use the hand terminal to
check or change the
setting in C0120
With U
= 100 %, the
0
acceleration time t
is
ir
deactivated
Use the hand terminal to
check or change the
setting in C0016
L