Top-Up, Operation With The Water Treatment Module; Malfunction Messages - Wilo Sinum MP M-2-50 Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 43
7.7. Top-up, operation with the water treatment module    
Maintenance
Wartung
11-5
Treatment
quantity reset
Perform action
Fig. FM.056.V01.15

7.8. Malfunction messages

Procedures and values for error identification,
evaluation and output have been tried in prac-
tice, prevent secondary failures and invite user
awareness. Please note that incorrect set-up
conditions can lead to repeated errors and inhibit
the intended use. Examples of incorrect set-up
conditions are: incorrect or no longer applicable
design, outdated equipment, incorrect installation
and inadmissible operational parameters.
Group error
Error, designation cause;
message
effect/action
menu line no.
-
Voltage spike sensor (short circuit)
-
Pressure sensor > 20 mA
Signal out of sensor range or short circuit, no pressure read-out;
lockshield valves in return connection in incorrect position /
check electrical installation, threaded round connector, sensor
range (4-20 mA; 16 bar), return connection, change sensor if
necessary
» service; Error off: self-resetting when error resolved.
-
Pressure sensor < 4 mA
Signal below sensor range or not connected, no pressure read-
out / check electrical installation, threaded round connector,
sensor range (4 -20 mA; 16 bar), change sensor if necessary »
service; Error off: self-resetting when error resolved.
-
Volume sensor > 20 mA
Signal out of sensor range or short circuit, no volume readout /
check electrical installation, threaded round connector, sensor
range (FSI 1: 150-300; 2: 400-800; 3: 1000-2000; 4: 2500-
5000; 5: 6500-10000), change sensor if necessary» service;
Error OFF: self-resetting when error resolved.
Installation and operating instructions Wilo-Sinum
Reset the treated quantity:
Required after each change of the
treatment module. Observe error
message nos.: 55; 61; 31; page 28.
When reset, the value in field 4 of the
operating menu [10] changes from
the previously processed quantity to:
00000 l
Caution:
Resetting to: 00000 l without replacing
the module, and without verifying the
residual capacity, leads to an unac-
ceptable quality of the top-up water!
Top-up
8-2-1
Treatment
activate
edit mode?
Default
Value
setting
ON
ON
ON
ON
Changing the treatment volume
Required if the default value (300 litres)
does not match the capacity of the
initial module, or the preset value of the
used module does not match the ca-
pacity of the module changed. (Impulse
water counter standard: 10 l / Imp.)
Caution:
The use of an incorrect value can lead
to unacceptable quality of the top-up
water or prevent the use remaining
capacities!
Perform action
Fig. FM.055.V01.15
Error message
number
1
2
3
4
English
25

Publicité

Table des Matières
loading

Table des Matières