9-21. Automatic Address Setting

9-21-1. Basic wiring diagram
Link wiring
N OTE
A terminal plug (black) is attached to each of the
outdoor unit control PCBs. At only one outdoor unit,
leave the terminal plug short-circuit socket on the "Yes"
side. At all the other outdoor units, change the socket
(from "Yes" to "No").
A maximum of 8 indoor units can be connected to 1 remote
controller for group control.
Fig. 9-15
Automatic address setting from the outdoor unit
Case 1
If the power can be turned ON separately for the indoor and
outdoor units in the system, the indoor unit addresses can be
set without running the compressor.
(1) Turn on the indoor and outdoor unit power for refrigerant
system 1.
Press and hold the automatic address setting button
(black) for 1 second or longer at the outdoor unit where the
power was turned ON.
Communication for automatic address setting begins.
LED 1 and 2 on the outdoor unit control PCB blink
alternately, and turn OFF when address setting is
completed.
<Approximately 4 – 5 minutes are
required.>
(2) Next, turn ON the power only at the indoor and outdoor
units in a different system. Press the automatic address
setting button (black) on the outdoor unit.
LED 1 and 2 on the outdoor unit control PCB blink
alternately, and turn OFF when address setting is
completed.
Repeat the same procedure for each system and complete
automatic address setting.
(3) Operation using the remote controller is now possible.
Case 2
If the power cannot be turned ON separately for the indoor
and outdoor units in the system:
The compressors must be run in order to automatically set
the indoor unit addresses. Therefore perform this step after
completing the refrigerant tubing work.
(1) Turn ON the power to the indoor and outdoor units in all
refrigerant systems.
When setting addresses in cooling mode
(2) Short-circuit the mode-change pin at the outdoor unit
where automatic address setting will be performed. Then
press the automatic address setting button (black).
When setting addresses in heating mode
(2) Press the automatic address setting button (black) at
the outdoor unit where automatic address setting will be
performed.
(3) LED 1 and 2 blink alternately. The compressors begin
running in Cooling (or Heating) mode. Communication for
automatic address setting begins, using the temperature
changes at the indoor units.
<All indoor units are in operating status.>
Address setting is completed when the compressors stop
and the LED indicators turn OFF. <Approximately 15
minutes is required for 1 system.>
If address setting fails, LED 1 and 2 blink simultaneously
and the alarm contents are displayed at the remote
controller.
(4) After 1 system is completed, be sure to press the
automatic address setting button (black) at the other
outdoor units to complete automatic address setting in the
same way for each system.
(5) Operation using the remote controller is now possible.
35
Automatic address setting using the remote controller
Case 3
If the power can be turned ON separately for the indoor and
outdoor units in each system (indoor unit addresses can be
set without running the compressor):
Individual system automatic address setting: Display item code
"A1".
(1) Press the remote controller timer time
button and
button simultaneously.
(Hold for 4 seconds or longer.)
(2) Then press either the temperature setting
or
button.
(Confirm that the item code is "A1".)
(3) Use either the
or
button to select the
outdoor unit to perform automatic address setting for. Then
press the
button.
("R.C.1" is displayed, and automatic address setting is
performed for refrigerant system 1.)
When automatic address setting for system 1 is completed,
the units return to normal stopped status.
<Approximately 4 – 5 minutes are required.>
During automatic address setting, "SETTING" blinks on the
remote controller display. This display disappears when
address setting is completed.
Case 4
If the power cannot be turned ON separately for the indoor
and outdoor units in each system:
(The compressors must be run in order to automatically set
the indoor unit addresses. Therefore perform this step after
completing the refrigerant tubing work.)
All-systems automatic address setting: Display item code "AA".
(1) Press the remote controller timer time
button and
button simultaneously. (Hold for 4 seconds or longer.)
(2) Next press the
button.
(Automatic address setting is performed in sequence for
all outdoor units from No. 1 to No. 30. When automatic
address setting is completed, the units return to normal
stopped status.)
<Approximately 15 minutes is required for each system.>
During automatic address setting, "SETTING" blinks on the
remote controller display. This display disappears when
address setting is completed.
Fig. 9-16
9-21-2. Setting outdoor unit system addresses
For the basic wiring diagram (Set the system addresses: 1, 2, 3...)
Outdoor unit control PCB
8 – 10 HP
System address rotary switch
(Set to "0" at time of shipment)
System address rotary switch
System address
10s
20s
DIP switch
ON
ON
1
2
OFF
8 – 10 HP
OC (CN500, BLU)
EMG (CN502, BRN)
63PH (CN027, WHT)
SILENT (CN037, WHT)
FUSE (0.5A, F500)
PUMP DOWN (CN048)
EXCT
(CN030, RED)
TEMINAL (CN205, BLK)
RC P
C2 (CN020, WHT)
(CN039, RED)
C1 (CN021, WHT)
IC002
TS (CN022, RED)
FUSE
(6.3A, F101)
TO (CN023, BLK)
TD (CN024, BLK)
MOV1
(CN300, WHT)
CTL2
MOV2
(CN202, GRN)
(CN301, BLK)
CTL1
LED (D041 EEPROM LED)
(CN203, GRN)
EEPROM
N . P . C H E C K
LED2
TEST (CN033, RED)
(CN046, RED)
LED1
C-CHK (CN035)
R.C.ADD. Rotary switch
A.ADD (CN047)
MODE (CN038)
R.C.ADD. DIP switch
IC001
D115
(POWER LED)
Fig. 9-17
System address
System address
System address
10s digit
1s place
No.
(2P DIP switch)
(Rotary switch)
Both OFF
"0" setting
ON
ON
0 Automatic address
(Setting at shipment = "0")
1
2
OFF
Both OFF
"1" setting
ON
ON
1 (If outdoor unit is No. 1)
1
2
OFF
36