Explosion protected built-in components
GHG 4. and GHG 2
1.6
Ex 28 control switch and GHG 249
ATEX type examination certificate:
Marking acc. to 94/9/EG and standard:
EN 60079-0
gas
gas
gas
gas
dust
IECEx type examination certificate:
Category of application:
IEC 60079-0
gas
gas
gas
gas
Staub
Operating termperature
Perm.ambient temperature in original packing:
Rated voltage:
rated supply
Rated current
terminals
20 A
20 A
16 A
10 A
Switching capacity acc. to AC 15 (EN 60947-5-1):
Switching capacity acc. to DC 13 (EN 60947-5-1):
Perm. short-circuit back-up fuse:
Design with gold-tipped contacts:
Number of poles:
Supply terminals:
Test torques supply terminals:
Weight:
BVS 14 ATEX E 076 U
-45 °C
II 2 G Ex de IIC Gb
-45 °C
II 2 G Ex de ib [ia/ib] IIC Gb
-55 °C
II 2 G Ex de IIB Gb
-55 °C
II 2 G Ex de ib [ia/ib] IIB Gb
-40 °C
II 2 D Ex tb [ia/ib] IIIC Db*
IECEx BVS 14.0047U
-45 °C
Ex de IIC Gb
-45 °C
Ex de ib [ia/ib] IIC Gb
-55 °C
Ex de IIB Gb
-55 °C
Ex de ib [ia/ib] IIB Gb
-40 °C
Ex tb [ia/ib] IIIC Db*
-55 °C
to
80 °C
-40 °C
60 °C
-55 °C
to
80 °C
to
690 V
T
40 °C
amb
6,0 mm²
62 °C
4,0 mm²
69 °C
2,5 mm²
72 °C
1,5 mm²
58 °C
230 V / 8,0 A
24 V / 6,0 A
25 A gL
bei
500 V
max. 400 mA
up to
16
pole
up to
20
pole at back side mounting
2x 0,5 - 4,0 mm²
1 x 1,0 - 6,0 mm²
2,5 Nm
1 level
1
ca.
0,25 kg
GB
T
50 °C
T
55 °C
amb
amb
72 °C
77 °C
79 °C
84 °C
82 °C
87 °C
68 °C
73 °C
400 V / 6,0 A
230 V / 0,4 A
fine / multi wire
(with pin terminal)
2
levels
3
levels
ca.
0,40 kg
ca.
0,55 kg
17