Dimensions, bus bar boxes
258
Bus bar box GHG 758 1
258
Bus bar box GHG 758 2
258
Bus bar box GHG 758 3
258
Bus bar box GHG 758 04
X = fixing dimensions
Explosion-protected terminal and bus bar boxes, switch,
type GHG 75.; Exko...
1.4

Pushbutton and switch

EC type examination certificate:
Rated voltage:
Rated current:
Switching capacity acc. to AC 15:
Switching capacity acc. to DC 13:
with gold-tipped contacts:
Terminals:
Weight:
1.5

Signal lamp

EC type examination certificate:
Rated voltage:
Lamp rating:
Terminals:
Weight:
1.6

Potentiometer

EC type examination certificate:
Rated voltage:
Rating:
Turning range:
Scale:
Terminals:
Weight:
1.7

AM45/AM72 measuring instrument:

EC type examination certificate:
Movement:
Measuring accuracy:
Overload range:
Measuring range:
L
:
i
C
:
i
U
:
i
I
:
i
Terminals:
AM 45 weight:
AM 72 weight:
1.8

Ex 23 control switch

EC type examination certificate:
Rated voltage:
Rated current:
Switching capacity acc. to AC 15:
Switching capacity acc. to DC 13:
Perm. short-circuit back-up fuse:
Design with gold-tipped contacts:
Terminals:
Weight:
1.9

Ex 29 control switch

EC type examination certificate:
Rated voltage:
Rated current:
Switching capacity acc. to AC 15:
Switching capacity acc. to DC 13:
Perm. short-circuit back-up fuse:
Design with gold-tipped contacts:
Supply terminals:
Weight:
IBExU14ATEX1030 U
up to max. 500 V
16 A
250 V / 6 A
500 V / 4.0 A
24 V / 6 A
60 V / 0.8 A
max. 400 mA
2 x 1.0 – 2.5 mm²
approx. 0.15 kg
IBExU 12ATEX 1047 U
12 - 240V AC / 20 - 250V AC /12 - 110V DC
0,6 W
2 x 1.0 – 2.5 mm²
approx. 0.15 kg
IBExU14ATEX1030 U
up to 250 V
1 W
270°
0 – 100%
2 x 1.0 – 2.5 mm²
approx. 0,15 kg
BVS 14 ATEX E 125U
Moving iron Ex -e
Moving coil Ex ib II
Class 2.5
Class 1.5
10-fold at – 25 sek.
10-fold at – 5 sek.
25-fold at – 4 sek.
50-fold at – 1 sek
telltale 1:1.5
n / 1 A
0 – 20 mA
0 - 25 A direct
4 – 20 mA
max. 0.1 mH
max. 0.1 nF
max. 30 V
max. 150 mA
2 x 1.5 - 4 mm²
0.35 kg
0.40 kg
BVS 13 ATEX E 107U
up to max. 500 V
10 A
230 V / 6 A
400 V / 4.0 A
24 V / 2 A
230 V / 0.5 A
16 A/gG at 500 V
max. 400 mA
2 x 0.5 - 2.5 mm²
1 level
2 levels
approx. 0.20 kg
approx. 0.35 kg
BVS 14 ATEX E 119 U
up to max. 500 V
16 A
With rated current ≥12 A the cross section is ≥ 2,5mm²
230 V / 6 A
400 V / 4.0 A
24 V / 2 A
230 V / 0.5 A
20 A/gG at 500 V
max. 400 mA
2 x 0.5 - 2.5 mm² or 1 x 1.0 - 6.0 mm²
1 level
2 levels
approx. 0.25 kg approx . 0.40 kg approx . 0.55 kg
GB
110 V / 0.5 A
3 levels
13