AREAS OF
APPLICATION
Submersible pumps in the MultiSt-
ream range are suitable for pumping
wastewater in municipal and industrial
pumping stations, and in rainwater re-
tention tanks.
MultiStream pumps are favoured for
use with:
- wastewater containing fibres
- wastewater containing solids
(without stones)
- mixed wastewater
- untreated water
- raw sludge
- surface water and rainwater
The submersible pumps are supplied
without explosion protection or with ex-
plosion protection.
When using the pumps, the relevant
national laws, regulations and stipula-
tions must be adhered to, for example:
∙ Installation of low-voltage systems
(e.g., VDE 0100 in Germany)
∙ Safety and working materials
(e.g., BetrSichV and BGR 500 in
Germany)
∙ Safety in wastewater systems
(e.g., GUV-V C5, GUV-R 104 and
GUV-R 126 in Germany)
∙ Electrical systems and operating
resources
(e.g., GUV-V A3 in Germany)
∙ Explosion protection
EN 60079-0, EN 60079-1, EN 60079-
14, EN 60079-17 and EN 1127-1
For non-standard utilisation conditions
in areas subject to explosion hazards,
please ask the local authority respon-
sible.
In Germany, this would be, for example,
the Trade Supervisory Centre (Gewer-
beaufsicht), the Technical Inspection
Agency (TÜV), the building authority
(Bauamt) or professional organisation
(Berufsgenossenschaft).
The installation and operation of this
equipment is regulated by the ordinance
concerning the protection of health and
safety in the provision of work equipment
and its use at work, concerning safety
when operating installations subject to
monitoring, and concerning the organi-
sation of industrial health and safety at
work, (Betriebs sicherheitsverordnung),
Article 1.
Where no explosion protection is stipu-
lated for the pumping of foul wastewa-
ter at the installation location, pumps
without explosion protection may also
be used.
Modes of operation
with the pumped medium at a tem-
perature of 40°C:
Motor submersed: continuous opera-
tion S1
Motor emerged: short duration opera-
tion S2; see "Technical Data"
Motor emerged: intermittent operation
S3; see "Technical Data"
The submersible pump is frost-resist-
ant down to -20°C when stored in dry
conditions. When installed, however,
it must not be allowed to freeze in the
water.

Transport

The pump must never be lifted
by the power supply cable! The
pump should only be lowered
by using a chain.
ELECTRICAL
CONNECTION
Circuitry
/
Alterations to the circuitry are to be
made using crimp connectors (X). The
new crimp connection must be profes-
sionally made.
By using our controls, you can be sure
that the requirements of the EU type-
testing certificate are met.
Only qualified electricians may
carry out electrical works to
the pump or the controls.
The standards applicable in each case
(e.g. EN), the country-specific regula-
tions (e.g. VDE in Germany), and the
regulations of the local supply network
operator must be observed.
ATTENTION! Never lay the end of ca-
bles in water! Penetrating water may
cause malfunctions.
ENGLISH
Only slow-blow fuses or automatic fus-
es with C or D characteristics are to be
used as pre-fuses for the pump. Nec-
essary fuse protection for for star-delta
start 35 A and 50 A for pumps 300...
The pump must be protected via an
overload trip. Setting for for star-delta
start = nominal current x 0.58.
If the protective device has been trig-
gered, the cause of the malfunction
must be eliminated before switching on
again.
Coil thermostats
ATTENTION! In addition to the overload
trip or protective switch of the motor,
the thermostats integrated in the motor
winding must also be connected. The
thermostats are suitable for 250 V / 1.2
A (cos phi = 0.6) and are labelled 30 and
32 for connection purposes.
Thermostat connection without ex-
plosion protection
The thermostats are to be connected in
such a way that the motor is switched
off via the control circuit when the re-
sponse temperature is reached. The
motor is switched on again automati-
cally after the winding has cooled down.
Thermostat connection with explo-
sion protection
The thermostats are to be connected in
such a way that the motor is switched
off via the control circuit when the re-
sponse temperature is reached. It must
not be possible for the motor to switch
on again automatically after the winding
has cooled down.
After an automatic cut-out via
the temperature limiters, the
cause of the malfunction must
first be eliminated. Only then may the
motor be switched on again manually.
The restart interlock must be "non-
resetting on power failure", i.e. the lock
must be in place to prevent restarting
even after a power cut (in Europe: Di-
rective 2014/34/EU, Appendix II 1.5, EN
60079-17 Table1, B10).
Operation with frequency converter
Frequency converters may only be used
for controlling the frequency of special
models of three-phase pumps.
ATTENTION! For physical reasons,
pumps may not be operated at a higher
frequency than that shown on the type
plate. If the frequency increases beyond
the value on the type plate, the power
9