Mounting air temperature probe

To position the temperature probe (ref. A):
-
pass the probe through the hole on the shoulder (ref. B)
4.3

Water probe management

If the board detects the water temperature probe in the battery
pocket on the appliance, start-up takes place normally. If the
probe is not connected, its absence is signalled with the red
and blue LEDs flashing simultaneously and the appliance will
not start.
To confirm operations without the probe, press the summer/
winter button for 5 seconds (ref A). This condition is stored
by the board for all subsequent start-ups.
4.4

Water connection on the right side versions motor connection

In the event one needs to invert the position of the hydraulic
battery connections from the left side to the right side of
the device, the electric connections box is also inverted,
but since the fan motor and the grid safety microswitch are
constrained in the original position, one must use the special
kit, available as an accessory.
The cable, equipped with male/female connectors, must be
connected on the right side to the motor and on the left side
CS035
V10
D
N
L
A
D
SPARE
T_ACQUA
E
TERMOSTATO
E_VALVE
V4
V3
V2
V1
EV
COM
E/I
MACHINE ONBOARD CONTROL ASSEMBLY AND CONNECTING
-
insert the probe in the lower hole (ref. C)
-
fix the probe in the special hook (ref. D).
C
In any case, once the probe is connected normal operations
are restored with temperature thresholds.
If the machine runs with the probe connected and the water
temperature is not suitable for active operations (above 20°C
in cooling or below 30°C in heating), ventilation is stopped
and the fault is signalled by the flashing of the corresponding
LED of the selected function (blue cooling C or red heating
D).
to the quick connector of the motor present on the board
(ref.D).
Also, the two terminals from the grid safety microswitch must
be extended and connected on the left side to contact S1
present on the board (ref.E).
The cables are fed through the back of the device through
the specific hole (ref.C).
B
C
EN
15