Télécharger Imprimer la page

Kessel Aqualift F Basic Instructions D'utilisation Et De Maintenance page 49

Masquer les pouces Voir aussi pour Aqualift F Basic:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 61
4.3
Overview of LED displays / information
ey
Flashing
Lights up / switched on
Switched off
Flashing alternately
flashing simultaneously
LED
1
2
3
4
Operating states
Alarm statuses / faults
* If the fault occurs again, inform the Customer Services department
2019/12
All manuals and user guides at all-guides.com
Acoustic
signal
(interval)
-
Ready for operation
-
System tank full, will be pumped out
shortly
-
Pumping system tank to empty
x
Battery fault
x
Power outage, no mains voltage, lifting
station has no function
x
Level fault, illogical sequence of levels
detected
x
Running time / number limit, wastewater
pump switch on to often or too long
x
Running time limit, maximum running
time for wastewater pump exceeded
x
Alarm level exceeded
Exceeded maximum switching cycles
Operation
Description
49 / 180
2
3
4
1
Aqualift Basic Mono
5
6
7
Ill. [41]
Action
No action necessary, wastewater
pump can be switched off with button
<8> (see manual operation 4.6)
Replace battery
Restore mains voltage, acknowledge
alarm (see 4.4)
Acknowledging the alarm (4.4)*
Wait until the level drops below the
alarm level again
Acknowledge alarm (4.4) and replace
control unit
8

Publicité

loading