250 V minimum, 25 A maximum inverse time circuit breakers
The max. voltage is limited to 240 V.
For 500 V systems:
500 V minimum, 25 A maximum, non-semiconductor fuses or
500 V minimum, 25 A maximum, inverse time circuit breakers
The max. voltage is limited to 500 V.
Group installation
For 240 V systems:
Suitable for group installation on a circuit capable of delivering not more than 18,000
rms symmetrical amperes when protected by 25 A maximum nonsemiconductor fuses,
Class RK5 and delivering not more than 5,000 rms symmetrical amperes when protec-
ted by 25 A maximum inverse time circuit breakers.
For 500 V systems:
Suitable for group installation on a circuit capable of delivering not more than 18,000
rms symmetrical amperes when protected by 25 A maximum nonsemiconductor fuses,
Class RK5 and delivering not more than 5,000 rms symmetrical amperes when protec-
ted by 25 A maximum inverse time circuit breakers.
Branch circuit protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
For maximum branch circuit protection see table below.
Series
Field Distributors
with attached
MOVIMOT
Motor overload protection
Motor overload protection is provided by MOVIMOT
MOVIMOT
thermal memory retention upon shutdown or power loss.
The trip current is adjusted to 140 % of the rated motor current.
Ambient temperature
The devices are suitable for an ambient temperature of 40 °C, max. 60 °C respectively
55 °C (Z.9 only) with derated output current. To determine the output current rating at
higher than 40 °C, the output current should be derated 3.0 % per °C between 40 °C
and 60 °C respectively 55°C (Z.9 only).
non-semiconductor fuses
250 V / 500 V minimum,
®
 MM..D
®
MM..D is provided with load and speed-sensitive overload protection and
Only use certified units with a limited output voltage (V
output current (I ≤ 8 A) as an external DC 24 V voltage source.
The UL certification only applies for the operation on voltage supply systems with
voltages to ground of max. 300 V. The UL-certification does not apply to operation
on voltage supply systems with a non-grounded star point (IT systems).
inverse time circuit breaker
25 A maximum
®
MM..D.