Videotec ULISSE RADICAL Manuel D'instructions page 17

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 81
7.4.2 120Vac and 230Vac power line
connection
Cut the cables to the correct length and make the
connections. Connect the power supply to the
terminal: CN1.
N
GND
a
Fig. 17
Connect the power supply cables as described in the
table below.
CONNECTION OF THE POWER SUPPLY LINE
Colour
Power supply 230Vac
Blue
Brown
Yellow/Green
Power supply 120Vac
Blue
Brown
Yellow/Green
Tab. 3
MNVCUPKHXL_2222_EN
CN1
L
Terminals
N (Neutral)
L (Phase)
N (Neutral)
L (Phase)
7.4.3 Connection of the alarm inputs, of
the twilight switch and of the relays
CAUTION! TNV-1 installation type. The
installation is type TNV-1, do not connect it
to SELV circuits.
CAUTION! In order to reduce the risk of fire,
only use UL Listed or CSA certified cables
with sections greater than or equal to
0.14mm² (26AWG).
Standard version
Fig. 18
Relay contact connection.
Fig. 19
Alarms connection.
Version with LED illuminators
CONNECTION OF THE ALARM INPUTS, OF THE TWILIGHT SWITCH
AND OF THE RELAYS
AL1, AL2, AL3,
Self-powered alarm inputs referring to the
AL4 e ALARMS
ALARMS common terminal
O1-C1 e O2-C2 Clean output contacts, can be activated by alarm
or by user control
Tab. 4
Connect the dusk switch to the ALARMS
and AL1 terminals. AL1 is the default alarm
contact for the light sensitive switch.
O1 C1 O2 C2
V
V
ALARMS
AL2
AL4
AL1
AL3
15