GENERAL NOTES
In Italy it is necessary to refer to the standard declaration of
conformity conforming to Ministerial Decree 37/2008 (pur-
suant to Law 46/1990) and standards UNI 10683/2012 and UNI
10412-2/2009.
In the case of installation in a multiple-tenancy building, con-
tact the building manager before installation.
In France, it is necessary to refer to Decree 2008-1231.
VERIFY COMPATIBILITY WITH OTHER DEVICES
In Italy the stove MUST NOT be installed in the same space
as type B gas heating equipment (e.g. gas boilers, stoves, and
equipment served by an extraction hood - ref. UNI 10683 and
7129).
In general, the stove could create low pressure in the room,
affecting the operation of such appliances or being affected by
them.
VERIFYTHE POWER SUPPLY CONNECTION
(the plug must be accessible)
The stove is supplied with a power cable that is to be connected
to a 230V 50 Hz socket, preferably fi tted with a magnetother-
mic switch. Voltage variations exceeding 10% can damage
the stove (unless already installed, an appropriate differential
switch must be fi tted). The electrical system must comply
with the law; particularly verify the effi ciency of the earthing
system. The power line must have a suitable cross-section for
the stove's power. An inadequate earthing system can cause
anomalies for which Edilkamin cannot be held liable.
In case of problems with the electrical grid, consult an electri-
cian to evaluate the installation of a sine-wave UPS of at least
800 Va.
Power variations greater than 10% can cause problems for the
product.
AIR INTAKE
The room where the stove is located must have an air intake
with cross section of at least 200 cm
of the air consumed by combustion.
Alternatively, the stove air may be taken directly from outside
through a 8 cm steel extension of the pipe.
In this case,there may be condensation problems and it is ne-
cessary to protect the air intake with a grille, which must have
a freesection of at least 50 cm².
The pipe must be less than 1 metre long and have no bends.
It must end with section at 90° facing downwards or be fi tted
with a wind guard. In any case all the way air intake duct must
be a free section of at least 50 cm².
The external terminal of the air inlet channel must be protected
with an anti-insect netting that does not reduce the 50 cm²
through passage.
INSTALLATION
2
to ensurereplenishment
- 33
POSITIONING AND DISTANCES FOR FIRE SAFETY
The stove must be installed in compliance with the following
safety conditions:
- minimum distance from fl ammable materials around the sides
and back of the stove: 20 cm
- fl ammable materials must not be placed less than 80 cm from
the front of the stove.
If it is not possible to comply with the above-mentioned di-
stances, technical and construction-related provisions must be
taken to prevent fi re hazards.
If connected to wooden walls or other fl ammable materials, the
smoke exhaust pipe must be insulated.
-