4.2.2 Setting the Station Addresses

DIP switch 1 to 7
NOTE
In the PROFIBUS-PA, each station is given an address. These addresses are
set
up using the DIP switches 1 to 7.
The permissible address range lies between 3 and 124
Settings:
DIP-1
DIP-2
ON
ON
OFF
OFF
ON
OFF
OFF
ON
* Delivery state: Address 126
NOTE

4.2.3 LED Display

The LED lights up when the unit is in cyclic data traffic.
Operating instructions no. 801 148
Bit 1 to Bit 7
The DIP switches are only read in when the unit is switched on.
DIP-3
DIP-4
OFF
OFF
ON
ON
ON
ON
ON
ON
If switch 8 is in the ON position, the internal address is used!
This address can be set up via the field bus.
DIP-5
DIP-6
DIP-7 Address
OFF
OFF
OFF
..
ON
ON
ON
ON
ON
ON
ON
ON
ON
3
124
125
126*
61