Battery Personalization; Personalization Using External Software - Eaton Pulsar Série Manuel D'installation Et D'utilisation

Masquer les pouces Voir aussi pour Pulsar Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4. Access to Maintenance and Personalization Data
Output Personalization
Function
Output voltage
(1)
Frequency converter
Output frequency
Transfer to the bypass
AC input
(1)
Overload level
(1)
ON/OFF Personalization
Function
Start on battery power Enabled
Automatic restart
Energy savings
Detection of phase/
neutral inversion
(SWF)

Battery Personalization

Function
Battery test
Selection of the
backup time
Battery protection
against excessive
discharges
4.4

Personalization Using External Software

Insert the Solution-Pac CD-ROM in the drive.
w
On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the
w
Personal Solution-Pac software.
Then select "Settings", "Advanced settings" and "UPS settings".
w
Note that the Linux/Unix/MacOS versions of the Personal Solution-Pac software do not offer this possibility.
(1). These Parameters may be modified only when the UPS is OFF.
(2). Bypass is disabled when frequency converter is enabled.
86-86710-00EN A02 - Page 22
Factory Setting
120 Volts AC
Disabled
(1)
Automatic selection
(1)
Bypass AC power must be
within tolances
102%
Factory Setting
Enabled
Disabled
Enabled
Factory Setting
Weekly test
Automatic detection of
number of battery modules
Enabled
Options
100/104/110/120/127 Volts AC
Enabled
(2)
50 or 60 Hz
Bypass AC power may be
outside tolerances
50 / 70%
Options
Disabled
Disabled
Enabled
Disabled
Options
No test / daily test / monthly
test
0 to 200 Ah
Disabled
Comments
The connected devices are never
transferred to the bypass.
User selectable only if the
frequency-converter function is
enabled.
Alarm if threshold is overrun.
Comments
The UPS restarts automatically
when AC power returns.
When function enabled, battery
shuts down when power drops
to <5%.
When function enabled, the UPS
remains OFF if the system detects
phase/neutral inversion.
Comments
UPS restarts automatically when
Normal AC source is restored.
When function disabled, EATON
warranty no longer applies.

Publicité

Table des Matières
loading

Table des Matières