5. Troubleshooting

Troubleshooting a UPS equipped with the HotSwap MBP module

Indication
The load is no longer supplied
when the rotary switch (53) on
the HotSwap MBP module is set
12
to the Bypass position.
The load is no longer supplied
when the rotary switch (53) on
13
the HotSwap MBP module is set
to the Normal position.
The load is no longer supplied
if AC power fails.
14
If a fault leads to UPS shutdown, press the ON/OFF button (27) to clear the fault.
5.2

Battery Module Replacement

Safety recommendations

Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the
required precautions. Risk of explosion if battery is replaced by an incorrect type. When replacing batteries, replace
with the same type and number of batteries or battery packs.
CAUTION:
Do not dispose of batteries in a fire. The batteries may explode. Dispose of used batteries according
to the instructions.
CAUTION:
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be
toxic.
CAUTION:
A battery can present a risk of electrical shock and high short circuit current. The following precau-
tions should be observed when working on batteries:
a.
Remove watches, rings, or other metal objects.
b.
Use tools with insulated handles.
c.
Wear rubber gloves and boots.
d.
Do not lay tools or metal parts on top of batteries.
e.
Disconnect charging source prior to connecting or disconnecting battery terminals.
f.
Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can
be reduced if such grounds are removed during installation and maintenance (applicable to equipment and
remote battery supplies not having a grounded supply circuit).
86-86710-00EN A02 - Page 24
Diagnostic
w The protected devices are con-
nected to the UPS output instead
of to the HotSwap MBP module.
w The AC power cord is connected
to the UPS input instead of to the
HotSwap MBP module.
w The UPS is shut down.
w The wiring between the UPS
and the HotSwap MBP module
is not correct.
w The rotary switch
on the
(53)
HotSwap MBP module is set to
the Bypass position.
w The wiring between the UPS
and the HotSwap MBP module
is not correct.
Correction
Check the wiring between the UPS
and the HotSwap MBP module (see
Section 2.6).
w Start the UPS.
w Check the wiring between the UPS
and the HotSwap MBP module (see
Section 2.6).
w Set the rotary switch
(53)
the HotSwap MBP module to the
Normal position.
w Check the wiring between the UPS
and the HotSwap MBP module (see
Section 2.6).
Ups is shutdown
w
on