Commissioning
3.2 Flowmeter connection using RS-232
1. Referring to the schematic below, wire the RS-232 Interface cable.
2. Connect the cable between the flowmeter and the PC using either the 9-pin, 25-pin or USB-
3. Refer to the flowmeter manual for details for accessing the Installation Menu.
RS-232 Interface Cable - RS-232 Connectors (use 9-pin or 25-pin)
The figure below is the schematic of the serial interface cable (MLFB P/N 7ME3960-0CS00)
needed to make the physical connection between the flowmeter and your PC. The wire ends
for the flowmeter terminations are stripped for easy insertion into TB2. Note that both
connectors have their CTS pin shorted to the RTS pin (pins 4-5 on 25-pin connector and pins
7-8 on 9-pin connector).
TB1
9-PIN SOLDER SIDE
25-PIN SOLDER SIDE
25-Pin Serial Connector
9-Pin Serial Connector
CABLE PIN 1015CPC-N
Figure 3-3
RS-232 Interface Cable Wiring
20
Note
Many newer Laptop PCs are not equipped with serial ports, having USB ports only. These
PCs will require a USB RS-232 adapter that can be purchased commercially. Not all of
these adapters are suitable.
the adapter from Radio Shack (part#26-183).
to-RS-232 cable connector, depending upon the port's architecture.
Siemens has found the best performance is achieved with
Red Wire
White Wire
Black Wire
TB2 of FUS1010
RX To Flowmeter
TX From Flowmeter
Operating Instructions, 12/2008, CQO:QSG002 Revision B
FUS1010 IP65 NEMA 4X Quick Start