10. Assembly Instructions

Warning!
Use the fitting only with non-return valves and the grit filters specified.
Failure to observe can result in an increased bacterial load in drinking water and
cause a health risk or even risk of death.
Important!
Before installing, flush the pipes in compliance with DIN 1988.
10.1 Install the screw connections (a).
10.2 Install the screw-rosettes (b).
10.3 Insert the grit filters (c).
Important!
Be careful to insert the grit filters the right way round.
10.4 Install the fitting (d) with the union nuts (e).
10.5 Open the water volume regulators (f).
10.6 Check the water connections for leaks.

11. Function

Triggering water flow
11.1 Press the button.
• Water flows.
• Water flow stops automatically after a set flow duration.
The flow duration can be set in the range 1–50s.
Selecting the temperature

12. Thermal Disinfection

This shower fitting provides the features necessary to perform thermal disinfection to
reduce the risk of Legionella infection.
Thermal disinfection is triggered by overturning the thermostat.
Warning!
Protective measures for persons (scald-protection) must be provided during thermal
disinfection, e.g. closing off sanitary rooms.
Failure to observe can cause bodily harm due to scalding.
The operator is responsible for performing, monitoring and logging (room, tap, date,
time, temperature, duration).
Any liability claims by third parties attributed to the operator improperly performing
thermal disinfection are therefore declined by the manufacturer.