6.5 Housing board description

Fig. 9

6.6 Ground connection

6.6.1 Earthing equipotential connection

The unit must be connected with an equipotential
bonding to the earth with an external cable having
the following minimum section: 4mm² (11AWG).
Connect the cable for equipotential connection with
the eyelet terminal provided.
The eyelet terminal is suitable for cables with a cross-
section of: from 4mm² (11AWG) up to 6mm² (9AWG).
Secure the eyelet terminal using the screw and
toothed washer supplied.
Characteristics of the screw (M6)
• Material: A4
• Screw head: ISO 4017
• Length: 16mm
14
Fig. 10

6.6.2 Connection of the safety earthing

The earthing cable must be connected to the internal
connector (16, 6.5 Housing board description, page
14).
MNVCEXH_2104_EN