Electrical installation

Power terminals

4.2
Power terminals
{
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Protective measures:
ƒ
(
Stop!
No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
All power connections are plug connections and are coded. The connector
ƒ
set for the ECSZE000X0B power supply modules must be ordered
separately.
Installation of cables acc. to EN 60204−1.
ƒ
The cables used must comply with the approvals required for the
ƒ
respective application (e.g. VDE, UL, etc.).
66
Death or severe injuries when the device is touched in the event
of a fault.
Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor
diameter ³ 10 mm
Destruction of the device if the mains voltage is too high.
Observe the maximally permissible mains voltage.
Fuse the device correctly on the supply side against mains
fluctuations and voltage peaks.
2
or PE conductor must be connected twice)
l
EDKCSEE040 DE/EN/FR 3.0