Terminal assignment

Terminal
X21
X21/L1
X21/L2
X21/L3
X21/PE
X22
X22/BR0
X22/BR1
X22/+UG
X22/+UG
X22/−UG
X22/PE
Cable cross−sections and screw−tightening torques
Cable type
Terminal strips X21 and X22
Rigid
Flexible
Shielded cables
The following factors decisively determine the effect of the shielded cables:
Good shield connection
ƒ
Ensure a contact surface as large as possible
Low shield resistance
ƒ
Only use shields with tin−plated or nickel−plated copper braids (shields
with steel braids cannot be used).
High overlap rate of the braid
ƒ
At least 70 ... 80 % with 90° overlap angle
The ECSZS000X0B shield mounting kit includes a wire clamp and shield sheet.
EDKCSEE040 DE/EN/FR 3.0
Function
Mains connection
Mains phase L1
Mains phase L2
Mains phase L3
Connection of PE conductor
DC−bus voltage connection
Internal brake resistor, connection 1
External brake resistor, connection 1
Internal/external brake resistor, connection 2
DC−bus voltage supply, plus
DC−bus voltage supply, minus
Connection of PE conductor
Wire end ferrule
Possible cable
cross−sections
0.2 ... 10 mm
˘
(AWG 24 ... 8)
Without wire end
0.2 ... 10 mm
ferrule
(AWG 24 ... 8)
With insulated wire
0.25 ... 6 mm
end ferrule
(AWG 22 ... 10)
With insulated
0.25 ... 4 mm
TWIN wire end
(AWG 22 ... 12)
ferrule
l
Electrical installation
Power terminals
Electrical data
Dependent on application and
type
0 ... 480 V
^
up to 31.3 A (
Dependent on application and
type
0 ... 770 V
^
up to 38.5 A (
Tightening torque
2
2
1.2 ... 1.5 Nm
2
(10.6 ... 13.3 lb−in)
2
4
59)
59)
Stripping length
5 mm for screw
connection
10 mm for spring
connection
67