Electrical installation

Control terminals

4.3
Control terminals
The supply of the control electronics requires an external 24 V DC voltage
ƒ
at terminals X6/+24 and X6/GND.
Connect the thermal detector of an external brake resistor to the
ƒ
terminals X6/T1 and X6/T2. If no external brake resistor is required,
jumper terminals X6/T1 and X6/T2.
(
Stop!
ƒ
ƒ
ƒ
ƒ
78
The control cables must always be shielded to prevent
interference injections.
The voltage difference between X6/AG, X6/GND and PE of the
axis module may maximally amount to 50 V.
The voltage difference can be limited by:
– overvoltage−limiting components or
– direct connection of X6/AG and X6/GND to PE.
The wiring has to ensure that for X6/DO1 = 0 (LOW level) the
connected axis modules do not draw energy from the DC bus.
Otherwise, the power supply module may be damaged.
l