Electrical installation

Control connection X26

4.3
Control connection X26
Terminal assignment
Terminal
X26
The charging current limitation is bridged if X26 = HIGH (24 V DC).
ƒ
The polarity does not influence the function of the charging current
ƒ
limitation.
Cable cross−sections and screw−tightening torques
Cable type
Flexible
For control cables, we recommend a cable cross−section of 0.25 mm
58
Function
Connection for bridging the charging current
limitation
Wire end ferrule
Without wire end ferrule
l
Electrical data
21.8 ... 30 V DC,
max. 1.5 A
Possible cable
Tightening torque
cross−sections
2
0.2 ... 2.5 mm
0.5 ... 0.8 Nm
(AWG 24 ... 12)
(4.4 ... 7.1 lb−in)
Stripping
length
5 mm
2
!
EDKCSDK002 DE/EN/FR 1.1