Lenze ECSEE Serie Instructions De Montage page 64

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4
Electrical installation
Installation according to EMC (installation of a CE−typical drive system)
Assembly
Connect the power supply modules, capacitor modules (optional), axis
ƒ
modules, RFI filters, and mains chokes to the earthed mounting plate with
a surface as large as possible.
Mounting plates with conductive surfaces (zinc−coated or stainless
steel) allow permanent contact.
Painted plates are not suitable for an EMC−compliant installation.
If you use the ECSxK... capacitor module:
ƒ
Install the capacitor module between the power supply module and the
axis module(s).
If the total cable length in the DC−bus connection is > 5 m, install the
capacitor module as close as possible to the axis module with the
greatest power.
Use of several mounting plates:
ƒ
Connect as much surface of the mounting plates as possible (e.g. with
copper bands).
Ensure the separation of motor cable and signal or mains cables.
ƒ
Avoid a common terminal/power strip for the mains input and motor
ƒ
output.
Lay the cables as close as possible to the reference potential. Freely
ƒ
suspended cables act like aerials.
Filters
Only use RFI filters and mains chokes which are assigned to the power supply
modules:
RFI filters reduce impermissible high−frequency interferences to a
ƒ
permissible value.
Mains chokes reduce low−frequency interferences which depend on the
ƒ
motor cables and their lengths.
64