Electrical installation
Power terminals
Mains connection
J
Warnings!
ƒ
ƒ
Replacing defective fuses
{
Danger!
Hazardous electrical voltage
Components can carry hazardous voltages up to 3 minutes after
power−off.
Possible consequences:
ƒ
Protective measures:
ƒ
70
Use UL−approved cables, fuses and fuse holders only.
UL fuse:
– Voltage 500 ... 600 V
– Tripping characteristic "H", "K5" or "CC"
Death or severe injuries when touching the device.
Replace fuses in the deenergised state only.
– Set controller inhibit (CINH) for all axis modules in DC−bus
operation and disconnect all power supply modules from the
mains.
l
EDKCSEE040 DE/EN/FR 3.0