Lenze ECSEE Serie Instructions De Montage page 85

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Bus cable length
)
Note!
The permissible cable lengths must be observed.
1. Check the compliance with the total cable length in Tab. 4−1.
The baud rate determines the total cable length.
CAN baud rate [kbit/s]
50
125
250
500
1000
Tab. 4−1
Total cable length
2. Check the compliance with the segment cable length in Tab. 4−2.
The segment cable length is determined by the cable cross−section used and the
number of nodes. Without a repeater, the segment cable length corresponds to
the total cable length.
Number of nodes
2
5
10
20
32
63
Tab. 4−2
Segment cable length
3. Compare the two values detected.
If the value detected from Tab. 4−2 is smaller than the total cable length to be
provided from Tab. 4−1 , repeaters must be used. Repeaters divide the total cable
length into segments.
,
Observe...
the information on the use of a repeater in the
CAN Communication Manual.
EDKCSEE040 DE/EN/FR 3.0
Connection of system bus (CAN)
Max. bus length [m]
1500
630
290
120
25
Cable cross−section
2
0.25 mm
0.5 mm
240 m
430 m
230 m
420 m
230 m
410 m
210 m
390 m
200 m
360 m
170 m
310 m
l
Electrical installation
2
2
0.75 mm
650 m
640 m
620 m
580 m
550 m
470 m
4
2
1.0 mm
940 m
920 m
900 m
850 m
800 m
690 m
85

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ecsee012Ecsee020Ecsee040

Table des Matières